Operating principle
The system works according to the ion-exchange principle: unpurified water flows through the pressure tank where ion-exchange layer (cationic and anionic resins) attracts calcium, magnesium, iron ions and organic compounds.
The raw water quantity flowing through the tank decreases purification ability of ion-exchange layer,therefore it must be periodically renewed by rinsing with a saturated salt solution. Saturated salt solution NaCl is obtained from the salt tablets. This process is called regeneration of the filter. Elements gathered during regeneration are washed up in the sewers. The softener is running in fully automatic mode. Regeneration (flushing) times are controlled automatically by the control mechanisms and electronic water meters.
The control mechanism of the system has all the functions to be able faultlessly adjust the unique settings for each client according to the results of water analyses, water pressure and other parameters.
Technical data:
Purification yields | 1,4...1,9 m3h or 23,3...31,7 l/min |
Maximum flow rate | 4,5 m3h |
Operating required minimum water pressure | 1,8 Bar |
Quantity of quartz stones | 7 kg |
Quantity of cationic resins | 40 l |
Quantity of anionic resins | 15 l |
Reagent (salt tablets) consumption per regeneration | 8...10 kg |
Duration of regeneration (flushing) | 70...90 min |
Inlet / outlet diameter of control mechanism | DN 1" external thread |
Wastewater outlet diameter | DN 3/4" external thread |
Control unit electrical connection | 220 V |